60°C | 75°C | 90°C | 60°C | 75°C | 90°C | |
AWG | THW | THW | ||||
TW | THWN | TW | THWN | |||
MCM | UF | USE | THHN | UF | USE | THHN |
COPPER | ALUMINUM | |||||
18 | 14* | |||||
16 | 18* | |||||
14 | 20* | 20* | 25* | |||
12 | 25* | 25* | 30* | 20* | 20* | 25* |
10 | 30* | 35* | 40* | 25* | 30* | 35* |
8 | 40 | 50 | 55 | 30 | 40 | 45 |
6 | 40 | 50 | 55 | 30 | 40 | 45 |
4 | 55 | 65 | 75 | 40 | 50 | 60 |
3 | 85 | 100 | 110 | 65 | 75 | 85 |
2 | 95 | 115 | 130 | 75 | 90 | 100 |
1 | 110 | 130 | 150 | 85 | 100 | 115 |
1/0 | 125 | 150 | 170 | 100 | 120 | 135 |
2/0 | 145 | 175 | 195 | 115 | 135 | 150 |
3/0 | 165 | 200 | 225 | 130 | 155 | 175 |
4/0 | 195 | 230 | 260 | 150 | 180 | 205 |
250 | 215 | 255 | 290 | 170 | 205 | 230 |
300 | 240 | 285 | 320 | 190 | 230 | 255 |
350 | 260 | 310 | 350 | 210 | 250 | 280 |
400 | 280 | 335 | 380 | 225 | 270 | 305 |
500 | 320 | 380 | 430 | 260 | 310 | 350 |
600 | 355 | 420 | 475 | 285 | 340 | 385 |
700 | 385 | 460 | 520 | 310 | 375 | 420 |
750 | 400 | 475 | 535 | 320 | 385 | 435 |
* Unless otherwise specifically permitted elsewhere in the National Electrical Code Book, the overcurrent protection for conductor types marked with an asterisk shall not exceed 15 amperes for No. 14, 20 amperes for No. 12 & 30 amperes for No. 10 copper; or 15 amperes for No. 12 & 25 amperes for No. 10 aluminum & copper-clad aluminum after any correction factors for ambient temperature & number of conductors has been applied.